NetPing Converter 0-20mA, 886A02
- 51.00 USD
The adapter is designed to connect analog sensors and is able to measure the flowing current, voltage and resistance.
- The range of voltage measurement 0..30 VDC ± 3%;
- The range of current measurement -30..30 mA ± 3%;
- The range of resistance measurement 0..29999 Ohm ± 3%;
- The power supply of the current loop: 12V 100 mA, 24V 30 mA;
- Powered from the host device;
- Connection interface: 1-wire;
- Operating temperature range: -30 C to + 50 C (without moisture condensation, normal air humidity).
This device is not intended for domestic use.
NetPing Converter 0-20mA with an analog interface 0-20mA, the 886A02 model is designed to measure voltage (0..30 VDC ± 3%), flowing current (-30..30 mA ± 3%) and resistance (0..29999 Ohm ± 3%), it is necessary for connecting current sensors, sensors with output voltage or sensors that change their resistance.
If a current loop is connected in reverse, (+) to the RS- contact, the current will go in the "opposite direction" through the sensor shunt connector, and the measured current will be with “a minus” (a negative sign). The error in measuring the voltage on the loop with this connection is not significant, 60mV at maximum measured current 30mA.
It is possible to measure voltage only by connecting it to the RS + terminal. In this case, the current will be 0, the resistance - "infinity".
The converter is connected to the RJ12 (1-wire) connector of the host device using a cable with an RJ12 cap at the end. The cable also carries power to the sensor.
In a NetPing device, the converter is displayed on the "Analog inputs" page of the web interface.
Please look into the User Guide of the device. The information on connecting the converter is provided in the “User Guide” document of the device to which it is connected. The information about the converter configuration and functionality is specified in the “Firmware Description” document for the device to which it is connected.
It is possible to connect up to four 886A02 converters to one NetPing device.
The converters are delivered with a 2-meter detachable cable with an
RJ12 cap at the end. The cable length can be increased by using an extension cable for 1-Wire sensors: Cable extender 1-wire, 10m, Cable extender 1-wire, 5m, Cable extender 1-wire, 2m. The maximum allowed length of a 1-wire network is limited to 50 meters. When you use NetPing 1-wire hub, R912R2, the total length can be increased up to 300 meters.
Basic parameters | |
Current measurement range | -30 .. 30 mA ±3% |
Loop power supply | 12VDC 100 mA, 24VDC 30 mA |
Resistance measurement range | 0 .. 29999 Ohm ±3% |
Functionality | |
Voltage measurement range | 0 .. 30 VDC ±3% |
Physical parameters | |
Device suit | a connecting cable with RJ12 connectors at the ends 2m, a terminal block STK-15EDGK-3.5-5P 1 pc., a screwdriver |
Device dimensions | 95 x 28 x 25 |
Operating temperature range | -30 .. +50°C (without moisture condensation, normal air humidity) |
Weight | 70 g |