NetPing 4 IP PDU GSM3G 64R701
- 357.00 USD
A device of power supply sockets remote management via Ethernet/Internet network (IP power distribution unit) with SMS management support.
- 4 controllable sockets (IEC320-C13);
- 2 x 10/100-BASE-TX Ethernet ports;
- A built-in 3G GSM modem for SMS management and notification;
- Built-in ionistor for the operation of the warning system in the absence of 220 V;
- Ability to connect the battery module;
- A metal body for installing into a 10' rack 1U or mounting on a flat surface;
- External 1-wire sensors can be connected: temperature, humidity, supply voltage, analog sensor adapter;
- 6 I/O lines for connecting external sensors of "dry contact" type;
- Operating temperature range: -30...50 °C (no condensation, normal humidity).
The device is not intended for domestic use.
NetPing 4 IP PDU GSM3G 64R701 is an IP PDU (IP Power Distribution Unit) device. These devices are designed to switch on/off and restart the equipment by managing 220V sockets. This device contains four independently controlled sockets, a built-in GSM modem for receiving SMS commands and sending SMS notifications, six 1wire ports with independent drivers, six input/output lines for connecting sensors of a “dry contact” and managing external executive devices. A built-in ionister allows a notification sending in case of a power failure. The possibility to connect an external battery module allows you to organize an uninterrupted power supply to the device in case of problems with the main power line.
NetPing 4 IP PDU GSM3G 64R701 is used for:
remote power control inside ATMs, vending machines, payment terminals and other similar equipment. At the same time, the device can monitor the internal operating conditions of the equipment (for example, it can monitor the operating temperature of the bill acceptor and it will not fall outside the permissible range), signal problems both via Ethernet and using SMS commands. In case of interruption of the external power supply, the device will stay connected using SMS messages and continue to monitor the status of the sensors;
rebooting the frozen modems, access points, routers, servers and other computer equipment without the need for physical access. If the network is not available, the operation can be performed via the SMS command. This allows you to save effort and costs on a lot of trips in order to turn on / off the frozen device;
remote rebooting the frozen modems, access points, routers, servers and other computer equipment without the need for physical access. If the network is not available, the operation can be performed via the SMS command;
remote turning on / off additional computer equipment. The physical turning on backup servers, routers, access points can be performed when necessary in manual or automatic modes and turning off them when you do not need it. This saves energy and reduces wearing of the equipment, which is required only occasionally or at specific intervals;
remote notifications in case of power failure on the distant site;
remote turning on / off conference monitors, monitors in a gaming club or an Internet cafe. Monitors can be controlled both via Ethernet / Internet and using SMS commands;
remote control of air conditioners, ventilation systems and climate control systems. Connected sensors allow you to monitor the current situation, and the remote control of 220 V sockets allows you to turn on the system you need without physical presence at the facility, including in an automatic mode.
Management of sockets and power inputs NetPing 4 IP PDU GSM3G 64R701
Remote Management of Device Sockets via the Ethernet/Internet Network
Each output socket of a device can be remotely switched on/switched off/reloaded. Sockets can be managed through a built-in web interface with the help of any browser, SNMP commands, and HTTP API.
Sockets Remote Management with the Help of SMS Messages
Any socket of a device can be switched on/off or reloaded with the help of an SMS message. It allows you to control a power supply of a connected device even when the Ethernet/Internet network is unavailable and does not function.
A Watchdog for Automatic Reloading of External Equipment
If an external device, a router, or an access point freezes sometimes, NetPing can automatically reload these devices. To do this, it constantly inquires indicated IP addresses via the ICMP protocol. If it gets no response, it will automatically reload a connected device by switching off/ on its power supply.
Switching on/off Sockets on a Schedule
This device can switch on and off voltage on its built-in sockets on its own on a weekly schedule, switch on/off voltage several times a day, use a special schedule for holidays. This may be useful for a daily/weekly forced reboot of external devices or for switching off not used equipment in a certain time of a day.
Plug-in sensors and monitoring functions of NetPing 4 IP PDU GSM3G 64R701:
Email, SNMP TRAP, Syslog notifications about sensors triggering
When the sensors connected to a device are triggered the device can send the following notifications:
Email - the device can send Email messages directly through an SMTP server. Both notifications about sensors triggering and periodical reports about sensors status are sent via Email.
SNMP TRAP - is convenient to use for integration with monitoring systems as well as for fulfilling automatic actions on a PC (for example, start playing an alarm) with the help of specific software.
Syslog - with the help of specific software installed on a PC (a syslog server), all messages from sensors can be stored in a text file for the following analysis and you can use the other possibilities of this standard.
SMS-Notifications from Sensors
When a sensor is triggered, the device can send an SMS notification to an indicated phone number. It is convenient to use for the most important sensors. A responsible employee will receive a notification to his/her cell phone regardless of his/her location and Internet access. In addition, the notification does not depend on the Ethernet/Internet access/connection of the device.
Temperature Sensors
External temperature sensors are extremely popular in monitoring systems. With their help, it is possible to control a temperature mode of an important equipment operation as well as receive timely notifications about denials and failures in a climate control system, diagnose coolers failures and accidental ventilation flows overlaps.
A Humidity Sensor
It allows estimating the relative humidity of atmospheric air. It is commonly used to monitor optimum conditions of a computer equipment operation in server rooms.
A Leakage Sensor
It is designed to detect liquid due to the leakage sensor cable connected to it, including in small volumes - up to a few drops. Compared to a point leakage sensor, a cable leakage sensor with a sensor cable allows you to create a complex system for detecting leaks around the perimeter and, as a result, prevent damage associated with flooding of premises and equipment.
Ease to use, easy integration into existing systems, reliability:
Works 24 hours/ 7 Days a Week, without Hang-ups
This device is designed for an uninterrupted operation in an unattended room in 24/7 mode. A built-in power supply supervisor protects the device from hang-ups when there are voltage fluctuations. We do not implement third-party resource-intensive operating systems into the device, the whole code is completely written by our specialists and is optimized as much as possible for this functionality.
The built-in ionistor for sending notifications about triggered sensors when the main power supply is cut off
If there is no main power supply, the device will continue to work from the built-in ionistor for a short time, the sensors will retain their operability. The device can notify the lack of the main power supply via SMS, Email or SNMP TRAP. The built-in ionistor will provide up to 1 minute of autonomous operation of the device (with the enabled Ethernet interface and sensors) and about 6 minutes of autonomous operation of the device with the disconnected Ethernet interface.
A built-in webserver
You can configure and manage the device via a browser. No special software is needed. The device works on any OS (Windows, Linux, Mac).
Connecting to an Ethernet Network, a Static IP Address
The device is connected to a common office Ethernet network, into any available port of an Ethernet switch. Having published an IP address of the device on the Internet, it is possible to manage device sockets from anywhere in the world.
2 Ethernet ports on the device case
These two ports allow you to use one port for connecting the device to an Ethernet switch, and the second port as a regular Ethernet port for connecting any Ethernet devices, including other NetPing devices, in a "chain". It can be especially useful when all the switch ports are already occupied: NetPing can be plugged into the switch, and a network device can be connected to a free NetPing Ethernet port.
Authorization and Access Restriction
Access to the web interface of the device is protected with a login and password, set by a user. You need to authorize to get to the web interface of the device. Besides, it is possible to restrict access to the device, having left access from a specified IP subnetwork only.
SNMP Support
An SNMP protocol is widely used in data collection systems for network equipment. This device supports management commands as well as receives information from sensors via an SNMP protocol. The device is easily integrated with network monitoring systems, such as Zabbix, PRTG Network Monitor, OpenNMS, Nagios, Cacti, The Dude, Monit and similar ones, which receive data on the status of sensors, connected to the device, via an SNMP protocol.
Syslog Support
This protocol together with special server software can be used for collecting text log files of different devices operation in the network, including NetPing devices. This can be very useful for collecting and analyzing statistics.
URL-encoded Commands Support
The device supports sockets management and receiving information from sensors with the help of specific HTTP commands. These commands allow you to manage the device from any web page, developed by the user, including any mobile application.
Firmware Update
The device supports updating firmware through the web interface of the device. We occasionally release updates for the firmware. The updates are free of charge.
Nonvolatile Log File
All events (switching devices on and off, information from sensors) are stored in nonvolatile memory. The information is stored even if the power supply cuts off.
Nonvolatile Clock and Time Synchronization with NTP
To execute commands in a fixed specific time (a module Schedule), it is crucially important for a clock not to shift. Time tags are used for records in a log file as well. A device has its own built-in nonvolatile clock and the possibility to automatically sync with an external time server via an NTP protocol.
Automation on the base of NetPing 4 IP PDU GSM3G 64R701:
Automation and Logic Rules Execution (LOGIC)
This device allows you to set certain logic rules, which will be executed by the device automatically. For example, to switch on voltage, to turn on a notification alarm or a signal lamp, when a temperature on a temperature sensor exceeds indicated values, and automatically turn off a notification when a temperature is back to normal. Such rules allow implementing a simple automation system on the basis of the device.
Automatic Management of External Devices via SNMP
Logic
rules built into devices allow you to control other NetPing devices
over the network by sending them a snmpset command when a condition is
triggered. This can be useful, for example, to switch on an
indication/notification in another building when a sensor is triggered
in a server room. It doesn't matter where the device with the sensor is
and where the display device is located: if they have a network
connection, the command will be executed.
Basic parameters | |
Static IP | Yes + Mac address |
Firmware update | by the user |
Ethernet port | 2 x 10/100 BASE-TX |
Fanless solution | Yes |
Built-in GSM modem | Yes, 3G GSM modem, only to send/receive SMS messages |
Power control | |
Number of independent power channels | 4 |
Number of power sources | 1 |
Short protect circuit | Fuse |
Summary output power | 3.5 kW |
Watchdog function | Yes |
Managing sockets on a schedule | Yes |
Individual socket output power | 1.5 kW |
Sensors | |
Adapters of Analogue sensors | Yes, 3 adapters, 1-wire |
Airflow sensors | up to 6 sensors |
Power quality monitoring sensors | Yes, up to 3 pcs of 1-wire sensors |
Input-Output lines | 6 |
1-wire sensors support | Yes |
Temperature sensors | up to 8 sensors |
Humidity sensors | Yes, 4 pcs of 1-wire humidity sensors |
220V sensors | up to 6 sensors |
Door sensors | up to 6 sensors |
Smoke sensors | up to 6 sensors |
Motion sensors | up to 6 sensors |
Buzzer | up to 1 sensor |
Managed NetPing AC/DIN socket | Up to 6 sockets |
Functionality | |
Built-in web server | Yes |
LOGIC support | Yes |
Sending notification when the power supply is cut off | Yes |
Email notifications | Yes |
Get time from NTP | Yes |
Internal log | Yes |
SMS notifications | Yes |
SMS commands | Yes |
SNMP control | Yes, SNMP v1 |
SNMP trap | Yes, SNMP v1/v2 |
Syslog support | Yes |
URL-encoded commands | Yes (HTTP API) |
Physical parameters | |
GSM antenna | ADA-900M-SMA-3,0m antenna (frequency 900/1800Mhz; cable RG174 3м; connector SMA; the height of the antenna 85mm; VSWR 1.5; input resistance 50 Ohm; maximum capacity 60W; amplification 3dBi; polarization vertical) |
Device suit | the device, terminals, a power cable, GSM antenna 1 pc, a screwdriver, a user guide |
Power plug | Euro plug, removable cable 1.8 m |
Device dimensions | 218 x 44 x 180 mm |
Package box dimensions | 499 x 243 x 63 mm |
Power voltage | 100..250 V, 50/60 Hz |
Operating temperature range | -30°C .. 50°C |
Weight | 1 025 g |
Own power consumption | 12 W |
Battery life | from a built-in ionistor up to 6 minutes |
Firmware upgrade | |
DKSF_544.2.4.E-5.npu | Download |
Additional technical files | |
DKSF_544.2.4_MB.mib | Download |
DKSF_544.2.4_OL.oidlib | Download |
User guide | |
Technical documentation NetPing 4 IP PDU GSM3G 64R701 | Go to |